FLM-Z1-R
AI

The **FLM-Z1-R** is an addressable Relay Module manufactured by **Bosch**, designed for use within their Fire Alarm Systems (FACP). It is a critical component used to interface the fire panel with external systems like elevators, HVAC units, and door closers.
---
### 1. Technical Specifications
Below are the primary electrical and physical specifications for the device:
| Feature | Specification |
| :--- | :--- |
| **Operating Voltage** | 15 VDC to 33 VDC |
| **Current Consumption** | < 0.2 mA (Standby) / 1.5 mA (Active LED) |
| **Contact Rating** | 2.0 A @ 30 VDC / 0.5 A @ 125 VAC |
| **Relay Type** | Form C (Dry Contact) |
| **Addressing Method** | Rotary Switches (000-254) |
| **Temperature Range** | -4°F to 122°F (-20°C to 50°C) |
---
### 2. Key Electronic Components & Design
The FLM-Z1-R consists of several integrated subsystems that allow it to communicate and perform switching tasks:
* **Integrated Microprocessor:** Manages the digital communication with the Fire Alarm Control Panel (FACP) using a proprietary protocol. It handles self-diagnostics and status reporting.
* **Rotary Addressing Switches:** Three decimal rotary switches on the front of the module allow for manual address setting. This ensures the panel can identify the specific location and function of the relay.
* **Form C Relay (Electromechanical):** The "R" in the model stands for Relay. It provides a set of **Normally Open (NO)** and **Normally Closed (NC)** contacts with a common terminal.
* **LED Status Indicator:** A built-in bicolor LED flashes green during normal polling and turns steady red when the relay is activated.
* **EEPROM:** Stores the device’s unique ID and configuration data, ensuring settings are preserved even during power loss.
---
### 3. Wiring Configuration
The module features specific terminals for the Signaling Line Circuit (SLC) and the controlled load:
1. **Terminals 1 & 2 (SLC In/Out):** Connects to the main loop of the Fire Alarm Control Panel.
2. **Terminals 3 & 4 (Relay Contacts):** Connection for the Common (C) and Normally Closed (NC) circuit.
3. **Terminals 5 & 6 (Relay Contacts):** Connection for the Common (C) and Normally Open (NO) circuit.
---
### 4. Safety & Compliance
* **Galvanic Isolation:** The electronic circuitry is isolated from the relay contacts to prevent external electrical surges from damaging the fire alarm loop.
* **Supervision:** The module is "supervised" by the panel; if the module is removed or fails, the FACP will trigger a "Trouble" condition.
- ⤷
What is the maximum current capacity for the relay contacts?
- ⤷ How do you set the address for this module?
- ⤷ Can this module be used for high-voltage switching applications?