2 / 6 page ![]() Littelfuse.com © 2019 Littelfuse, Inc. Rev: 1-B-050420 2 of 6 Protection Relays & Controls NGR SERIES – CANADA Simplified Circuit Diagram with Littelfuse Neutral-Grounding-Resistor Monitor NGR L2 CT L1 ER Series Sensing Resistor NGR Monitor Note 2 Note 1 Transformer or Generator Neutral (XO) Note 4 Note 5 Note 3 Note 6 NGR SYSTEM Note 1: Use minimum #8 AWG white or grey conductor insulated to system voltage to connect NGR to neutral. Note 2: Use conductor insulated to system voltage (#14 AWG is typically used) and a separate lug at the X0 point to connect ER Series Sensing Resistor to neutral. Note 3: Locate NGR system near transformer or generator. Note 4: Two-conductor twisted cable required, shielded recommended. Note 5: Voltage between ER Series Sensing Resistor terminals R and G is limited to 100 V by internal clamp. Note 6: Use minimum #8 AWG green or bare conductor to connect NGR to ground. |
|
|
リンク URL |
| ALLDATASHEETはお客様のビジネスに役立ちますか? [ DONATE ] |
Alldatasheetは | 広告 | お問い合わせ | プライバシーポリシー | データシートへのリンク | リンク交換 | メーカーリスト All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|