7 / 24 page ![]() Liquisys M CCM223/253 Endress+Hauser 7 Controller Alarm Function (adjustable): Pulse-length/pulse-frequency controller, three-point step controller for Cl2/ClO2 Controller response: P, PI, PD, PID, basic load dosing Controller gain Kp: 0.01 to 20.00 Integral action time Tn: 0.0 to 999.9 min Derivative action time Tv: 0.0 to 999.9 min Period length of pulse-length controller: 0.5 to 999.9 s Frequency for pulse-frequency controller: 60 to 180 min-1 Basic load: 0 to 40% of max. set value Motor run time for three-point step controller: 10 to 999 s Neutral zone for three-point step controller: 0 to 40 % Function (switchable): Latching/momentary contact Alarm threshold adjustment range: Cl2/ClO2/pH/ORP/temperature: total measuring range Alarm delay: 0to2000s (min) Monitoring time lower limit violation: 0 to 2000 min Monitoring time upper limit violation: 0 to 2000 min |
|
|
リンク URL |
| ALLDATASHEETはお客様のビジネスに役立ちますか? [ DONATE ] |
Alldatasheetは | 広告 | お問い合わせ | プライバシーポリシー | データシートへのリンク | リンク交換 | メーカーリスト All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|