Back Button E5CS-R1KJX-F Datasheet HTML 2Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 3Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 4Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 5Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 6Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 7Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 8Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 9Page - Omron Electronics LLC E5CS-R1KJX-F Datasheet HTML 10Page - Omron Electronics LLC  
Zoom Inzoom in Zoom Outzoom out
 6 / 10 page
background image
Temperature Controller
E5CS--X
A--151
Precautions
The E5CS-X temperature controller has self-diagnostic functions that display the following error messages to simplify troubleshooting.
Message
Cause
Control output
fff
(1) Temperature has risen beyond temperature scale range
(2) Thermistor has been short-circuited
OFF during heating (reverse) operation
ON during cooling (normal) operation
---
(1) Temperature has fallen below temperature scale range
(2) Thermistor has broken
ON during heating (reverse) operation
OFF during cooling (normal) operation
fff (blinks)* (1) Failure has occurred in thermocouple or platinum RTD
(2) Temperature has risen much beyond scale range
OFF
--- (blinks)* (1) Failure has occurred in platinum RTD
(2) Polarities (positive and negative) of thermocouple are reversed
(3) Temperature has fallen much below scale range
OFF
e11 or e33* (1) Memory failure (E11) display
(2) Analog-to-digital converter failure (E33) display
Temperature controller must be repaired if recovery is not made
by turning power off once and on again.
Both control outputs and the alarm output
are OFF
Note: *Key operations are disabled.
When the alarm outputs are used, an alarm output occurs when the “FFF” and “------” messages appear in the display. These dis-
plays indicate when the temperature has risen beyond or fallen below the temperature scale range.
J Sensor Failure Indication
Condition
Display
Control output
Thermocouple sensor
Break in sensor
fff blinks
OFF
Short-circuit
Ambient temperature
OFF
Platinum RTD sensor
Break in sensor
fff blinks
OFF
--- blinks
OFF
Disconnection of two or three wires
fff blinks
OFF
Short-circuit
--- blinks
OFF
Thermistor sensor
Break in sensor
---
ON during heating (reverse) action
OFF during cooling (normal) action
Short-circuit
fff
ON during heating (reverse) action
OFF during cooling (normal) action
Note: The resistance of the platinum RTD is 100
Ω at 0°C and increases to 140 Ω at 100°C.



Html Pages

1 2 3 4 5 6 7 8 9 10


データシート ダウンロード

Go To PDF Page


リンク URL



ALLDATASHEETはお客様のビジネスに役立ちますか?  [ DONATE ] 

Alldatasheetは   |   広告   |   お問い合わせ   |   プライバシーポリシー   |   データシートへのリンク    |   リンク交換   |   メーカーリスト
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com